| Product Definition | Switching medium | A sealed vacuum interrupter extinguishes the arc when the circuit current is interrupted. | No insulating oil or SF₆ gas is required inside the interrupter, reducing fire and gas-handling concerns. |
| Electrical Ratings | Common rated voltage classes | 3.6 kV, 7.2 kV, 12 kV, 17.5 kV, 24 kV and 36 kV are widely used medium-voltage classes. | The selected voltage class must match the system’s highest operating voltage and insulation requirements. |
| Electrical Ratings | Rated normal current | Common medium-voltage configurations typically range from 630 A to 3,150 A; higher ratings are available for specialized designs. | The rating indicates the continuous current the breaker can carry under specified service conditions. |
| Fault Protection | Rated short-circuit breaking current | Typical medium-voltage products are commonly specified from 16 kA to 50 kA, depending on voltage and construction. | This value defines the maximum symmetrical fault current the breaker is designed to interrupt at its rated voltage. |
| Operating Mechanism | Operating technology | Spring-operated mechanisms are widely used; both fixed and withdrawable arrangements are available. | Withdrawable versions simplify isolation, inspection and maintenance in metal-enclosed switchgear. |
| Service Life | Mechanical endurance | Many medium-voltage designs are rated for approximately 10,000 mechanical operating cycles; higher endurance classes may be offered. | Endurance should be checked against the required switching frequency and duty cycle. |
| Applicable Standards | International and Chinese standards | IEC 62271-100 covers high-voltage alternating-current circuit breakers; GB/T 1984 is the corresponding Chinese circuit-breaker standard. | Standards define testing, ratings, insulation coordination, breaking performance and verification requirements. |
| Manufacturing Capability | Component supply chain | China has extensive industrial capacity for vacuum interrupters, copper conductors, insulating parts, operating mechanisms, sensors and switchgear assemblies. | A broad domestic supply base supports product customization, volume production and replacement-part availability. |
| Production Advantage | Industrial manufacturing scale | Large-scale electrical-equipment manufacturing, established metalworking capacity and mature export logistics support competitive production. | Scale can reduce unit cost and shorten lead times, although quality depends on design, testing and process control. |
| Customization | Configuration options | Common options include fixed or withdrawable mounting, top or bottom cable entry, motorized operation, undervoltage release and auxiliary contacts. | Configuration flexibility helps match the breaker to distribution panels, industrial systems and renewable-energy installations. |
| Typical Applications | End-use sectors | Utility distribution, industrial plants, commercial buildings, mining, rail transit, data centers and renewable-energy collection systems. | Vacuum circuit breakers are suited to frequent medium-voltage switching and short-circuit protection. |
| Supplier Evaluation | Key qualification criteria | Verify type-test evidence, routine-test procedures, rated values, insulation levels, endurance class, service support and compliance documentation. | Technical certification and test documentation are more reliable selection criteria than price or production capacity alone. |